CEC 334.30
Load center j-box shall be securely fastened in place.

CEC 334.30
3 wire range circuit not allowed on new installations.

CEC 334.30
Splice must be made in j-box.

CEC 334.30
Broken boxes with exposed support or support on the inside of the box.

CEC 334.30
NMC shall be secured by staples or similar fasteners, in a manner that is not damaging the cable, support at intervals not exceending 4 1/2 feet and within 12 inches of every j-box, cabinet or fitting.

CEC 300.4
Nail plates required when NMC is installed in bored or notched holes less than 1 1/4 inches from face of stud.

CEC 300.4 (D)
NMC must maintain 1 1/4 inches spacing when running parallel to framing members.

CEC 250.24 (A)(5)
Load center should have ground bar. Separate grounds and neutrals at sub panel.

CEC 110.12 (C)
Replace broken j-boxes.

CEC 314.17 (B)
NM connectors required on aluminum conductors on breaker terminals.

CEC 110.3 (B)
Breaker has two wires terminate on one lug.

CEC 110.12 (A)
Install KO seals at sub panel.

CEC 314.20
J-box is more than 1/4 inch recessed into the wall.

CEC 112.12 (A)
Close unused openings at j-box.

CEC 334.30
Inhibitor compound required on aluminum conductors on breaker terminals.

CEC 334.30
J-boxes of sufficient size to provide free space for all enclosed conductors.

CEC 334.30
At least 6 inches of free conductors at outlets.

CEC 334.30
Make-up not complete at light fixture.

CEC 334.30
NMC sheathing shall not extend less than 1/4 inch inside j-box.

CEC 334.30
Grounding conductors must be spliced by approved means.

 